Home Departments Electric  Electric Outage Reports

ElectricOutages full sm

Below are the most recent electric outages in the Borough of Kutztown.
To report an outage, please call 610-683-6131:

Date and Approximate Time: Thursday, May 25, 2017 at 12:00pm
Approximate Outage Length: 30 minutes
Outage Area: S. Laurel Street
Cause:
Squirrel contacted arrestor lead blowing line fuse

Date and Approximate Time: Tuesday, May 16, 2017 at 3:50pm
Approximate Outage Length: 50 minutes
Outage Area: 50 Normal Ave. Tripped Line 702, west end of town
Cause:
Blown Lightning Arrestor tripped line and blew transformer fuse

Date and Approximate Time: Saturday, February 25, 2017 at 4:15pm
Approximate Outage Length: Varied, average 2 hours
Outage Area: Locked out Line 701, east end of town
Cause:
Low Cable TV wire was caught by truck, snapping pole in James Alley

Date and Approximate Time: Monday, August 29, 2016 at 5:30pm
Approximate Outage Length: 2 Hours
Outage Area: 61 Constitution Blvd, Bieber Alley
Cause: Tree branch on wires

Date and Approximate Time: Thursday, August 11, 2016 at 7:15am
Approximate Outage Length:
45 Minutes
Outage Area:
West end of town, Line 702
Cause:
Bird contacted arrestor lead locking out Line 702 recloser

Date and Approximate Time: Friday, July 29, 2016 at 8:15pm
Approximate Outage Length: 1 Hour, 10 Minutes
Outage Area: Line 701 East end of town
Cause: Lightning strike caused broken cutout and blow arrestor, locking out 701 Recloser

Date and Approximate Time: Saturday, July 9, 2016 at 8:33pm
Approximate Outage Length:
1 Hour, 15 Minutes
Outage Area: 200 block Highland, 200 block E. Walnut, N. Laurel Street
Cause: Lightning struck pole, blown fuse cutout

Date and Approximate Time: Wednesday, June 15, 2016 at 6:53am
Approximate Outage Length: 28 Minutes
Outage Area: 400 blocks Vine Alley and W. Walnut
Cause: Squirrel contacted transformer lead blowing fuse

Date and Approximate Time: Monday, June 13, 2016 at 7:40pm
Approximate Outage Length:
1 Second
Outage Area: Line 701 East end of town
Cause: Bird contacted arrestor lead tripping Line 701

Date and Approximate Time: Thursday, June 9, 2016 at 9:55am
Approximate Outage Length: 65 Minutes
Outage Area: Garden Apartments, Building C
Cause: Animal contacted primary wire blowing fuse to Building C and tripping Line 703

Date and Approximate Time: Monday, May 31, 2016 at 6:52am
Approximate Outage Length: 70 Minutes
Outage Area: 200 block E. Main and E. Walnut
Cause: Bird contacted arrestor lead blowing transformer fuse

Date and Approximate Time: Monday, May 31, 2016 at 12:00am
Approximate Outage Length: 10 Seconds
Outage Area: Line 702 West, northwest end of town
Cause: Squirrel contacted arrestor lead causing 702 line to trip

Date and Approximate Time: Friday, May 27, 2016 at 7:30am
Approximate Outage Length: 30 Minutes
Outage Area: 200/300 blocks of S. Whiteoak and Pennsylvania Ave.
Cause: Squirrel contacted primary lines blowing line fuse

Date and Approximate Time: Saturday, May 21, 2016 at 6:47am
Approximate Outage Length: 1-2 Seconds
Outage Area: Trip on Line 701 east end of town
Cause: Squirrel contacted primary lines on pole #701-46 on Broad St.

Date and Approximate Time: Saturday, April 23, 2016 at 8:05am
Approximate Outage Length: 1-2 Seconds
Outage Area: Trip on Line 702 West, Northwest end of town
Cause of Outage: Blown lightning arrestor at 46 East Normal Ave.